CVE-2025-40820 1 Siemens 16 Sidoor Atd430w, Sidoor Ate530s Coated, Simatic and 13 more 2026-04-15 7.5 High
Affected products do not properly enforce TCP sequence number validation in specific scenarios but accept values within a broad range. This could allow an unauthenticated remote attacker e.g. to interfere with connection setup, potentially leading to a denial of service. The attack succeeds only if an attacker can inject IP packets with spoofed addresses at precisely timed moments, and it affects only TCP-based services.
CVE-2024-52285 1 Siemens 2 Sipass Integrated Ac5102 (acc-g2), Sipass Integrated Acc-ap 2026-04-15 5.3 Medium
A vulnerability has been identified in SiPass integrated AC5102 (ACC-G2) (All versions < V6.4.8), SiPass integrated ACC-AP (All versions < V6.4.8). Affected devices expose several MQTT URLs without authentication. This could allow an unauthenticated remote attacker to access sensitive data.
CVE-2024-52334 1 Siemens 1 Syngo Plaza Vb30e 2026-04-15 5.3 Medium
A vulnerability has been identified in syngo.plaza VB30E (All versions < VB30E_HF07). The affected application does not encrypt the passwords properly. This could allow an attacker to recover the original passwords and might gain unauthorized access.
CVE-2024-30207 1 Siemens 1 Simatic Rtls Locating Manager 2026-04-15 10 Critical
A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). The affected systems use symmetric cryptography with a hard-coded key to protect the communication between client and server. This could allow an unauthenticated remote attacker to compromise confidentiality and integrity of the communication and, subsequently, availability of the system. A successful exploit requires the attacker to gain knowledge of the hard-coded key and to be able to intercept the communication between client and server on the network.
CVE-2024-31484 1 Siemens 2 Cpc80 Central Processing\/communication, Cpci85 Central Processing\/communication 2026-04-15 7.8 High
A vulnerability has been identified in CPC80 Central Processing/Communication (All versions < V16.41), CPCI85 Central Processing/Communication (All versions < V5.30), CPCX26 Central Processing/Communication (All versions < V06.02), ETA4 Ethernet Interface IEC60870-5-104 (All versions < V10.46), ETA5 Ethernet Int. 1x100TX IEC61850 Ed.2 (All versions < V03.27), PCCX26 Ax 1703 PE, Contr, Communication Element (All versions < V06.05). The affected devices contain an improper null termination vulnerability while parsing a specific HTTP header. This could allow an attacker to execute code in the context of the current process or lead to denial of service condition.
CVE-2024-22040 1 Siemens 14 Cerberus Pro En Engineering Tool, Cerberus Pro En Fire Panel Fc72x, Cerberus Pro En X200 Cloud Distribution and 11 more 2026-04-15 7.5 High
A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions), Cerberus PRO EN Fire Panel FC72x IP6 (All versions), Cerberus PRO EN Fire Panel FC72x IP7 (All versions), Cerberus PRO EN Fire Panel FC72x IP8 (All versions < IP8 SR4), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.3.5618), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.3.5617), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions), Sinteso FS20 EN Fire Panel FC20 MP8 (All versions < MP8 SR4), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.3.5618), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.3.5617), Sinteso Mobile (All versions). The network communication library in affected systems insufficiently validates HMAC values which might result in a buffer overread. This could allow an unauthenticated remote attacker to crash the network service.
CVE-2024-41798 1 Siemens 1 Sentron Pac3200 2026-04-15 9.8 Critical
A vulnerability has been identified in SENTRON 7KM PAC3200 (All versions). Affected devices only provide a 4-digit PIN to protect from administrative access via Modbus TCP interface. Attackers with access to the Modbus TCP interface could easily bypass this protection by brute-force attacks or by sniffing the Modbus clear text communication.
CVE-2024-52504 1 Siemens 1 Siprotec 4 2026-04-15 7.5 High
A vulnerability has been identified in SIPROTEC 4 6MD61 (All versions), SIPROTEC 4 6MD63 (All versions), SIPROTEC 4 6MD66 (All versions), SIPROTEC 4 6MD665 (All versions), SIPROTEC 4 7SA522 (All versions), SIPROTEC 4 7SA6 (All versions < V4.78), SIPROTEC 4 7SD5 (All versions < V4.78), SIPROTEC 4 7SD610 (All versions < V4.78), SIPROTEC 4 7SJ61 (All versions), SIPROTEC 4 7SJ62 (All versions), SIPROTEC 4 7SJ63 (All versions), SIPROTEC 4 7SJ64 (All versions), SIPROTEC 4 7SJ66 (All versions), SIPROTEC 4 7SS52 (All versions), SIPROTEC 4 7ST6 (All versions), SIPROTEC 4 7UM61 (All versions), SIPROTEC 4 7UM62 (All versions), SIPROTEC 4 7UT612 (All versions), SIPROTEC 4 7UT613 (All versions), SIPROTEC 4 7UT63 (All versions), SIPROTEC 4 7VE6 (All versions), SIPROTEC 4 7VK61 (All versions), SIPROTEC 4 7VU683 (All versions), SIPROTEC 4 Compact 7RW80 (All versions), SIPROTEC 4 Compact 7SD80 (All versions), SIPROTEC 4 Compact 7SJ80 (All versions), SIPROTEC 4 Compact 7SJ81 (All versions), SIPROTEC 4 Compact 7SK80 (All versions), SIPROTEC 4 Compact 7SK81 (All versions). Affected devices do not properly handle interrupted operations of file transfer. This could allow an unauthenticated remote attacker to cause a denial of service condition. To restore normal operations, the devices need to be restarted.
CVE-2024-37997 1 Siemens 2 Jt Open, Plm Xml Sdk 2026-04-15 7.8 High
A vulnerability has been identified in JT Open (All versions < V11.5), JT2Go (All versions < V2406.0003), PLM XML SDK (All versions < V7.1.0.014), Teamcenter Visualization V14.2 (All versions < V14.2.0.13), Teamcenter Visualization V14.3 (All versions < V14.3.0.11), Teamcenter Visualization V2312 (All versions < V2312.0008), Teamcenter Visualization V2406 (All versions < V2406.0003). The affected applications contain a stack based overflow vulnerability while parsing specially crafted XML files. This could allow an attacker to execute code in the context of the current process.
CVE-2025-23403 1 Siemens 2 Simatic Ipc Diagbase, Simatic Ipc Diagmonitor 2026-04-15 7 High
A vulnerability has been identified in SIMATIC IPC DiagBase (All versions), SIMATIC IPC DiagMonitor (All versions). The affected device do not properly restrict the user permission for the registry key. This could allow an authenticated attacker to load vulnerable drivers into the system leading to privilege escalation or bypassing endpoint protection and other security measures.
CVE-2025-40805 1 Siemens 24 Industrial Edge Cloud Device (iecd), Industrial Edge Device Kit, Industrial Edge Own Device (ieod) and 21 more 2026-04-15 10 Critical
Affected devices do not properly enforce user authentication on specific API endpoints. This could facilitate an unauthenticated remote attacker to circumvent authentication and impersonate a legitimate user. Successful exploitation requires that the attacker has learned the identity of a legitimate user.
CVE-2023-32736 1 Siemens 9 Simatic S7-plcsim, Simatic Step 7, Simatic Wincc and 6 more 2026-04-15 7.3 High
A vulnerability has been identified in SIMATIC S7-PLCSIM V16 (All versions), SIMATIC S7-PLCSIM V17 (All versions), SIMATIC STEP 7 Safety V16 (All versions), SIMATIC STEP 7 Safety V17 (All versions < V17 Update 8), SIMATIC STEP 7 Safety V18 (All versions < V18 Update 5), SIMATIC STEP 7 V16 (All versions), SIMATIC STEP 7 V17 (All versions < V17 Update 8), SIMATIC STEP 7 V18 (All versions < V18 Update 5), SIMATIC WinCC Unified V16 (All versions), SIMATIC WinCC Unified V17 (All versions < V17 Update 8), SIMATIC WinCC Unified V18 (All versions < V18 SP5), SIMATIC WinCC V16 (All versions), SIMATIC WinCC V17 (All versions < V17 Update 8), SIMATIC WinCC V18 (All versions < V18 SP5), SIMOCODE ES V16 (All versions), SIMOCODE ES V17 (All versions < V17 Update 8), SIMOCODE ES V18 (All versions), SIMOTION SCOUT TIA V5.4 SP1 (All versions), SIMOTION SCOUT TIA V5.4 SP3 (All versions), SIMOTION SCOUT TIA V5.5 SP1 (All versions), SINAMICS Startdrive V16 (All versions), SINAMICS Startdrive V17 (All versions), SINAMICS Startdrive V18 (All versions), SIRIUS Safety ES V17 (TIA Portal) (All versions < V17 Update 8), SIRIUS Safety ES V18 (TIA Portal) (All versions), SIRIUS Soft Starter ES V17 (TIA Portal) (All versions < V17 Update 8), SIRIUS Soft Starter ES V18 (TIA Portal) (All versions), TIA Portal Cloud V16 (All versions), TIA Portal Cloud V17 (All versions < V4.6.0.1), TIA Portal Cloud V18 (All versions < V4.6.1.0). Affected products do not properly sanitize user-controllable input when parsing user settings. This could allow an attacker to cause a type confusion and execute arbitrary code within the affected application.
CVE-2024-32014 1 Siemens 1 Spectrum Power 4 2026-04-15 4.7 Medium
A vulnerability has been identified in Spectrum Power 4 (All versions < V4.70 SP12 Update 2). The affected application is vulnerable to alter the local database which contains the application credentials. This allows an attacker to gain administrative application privileges.
CVE-2011-20002 1 Siemens 3 Simatic, Simatic S7-1200, Simatic S7-1200 Cpu 2026-04-15 7.4 High
A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.2), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.2). Affected controllers are vulnerable to capture-replay in the communication with the engineering software. This could allow an on-path attacker between the engineering software and the controller to execute any previously recorded commands at a later time (e.g. set the controller to STOP), regardless whether or not the controller had a password configured.
CVE-2025-40584 1 Siemens 3 Simotion Scout, Simotion Scout Tia, Sinamics Starter 2026-04-15 5.5 Medium
A vulnerability has been identified in SIMOTION SCOUT TIA V5.4 (All versions), SIMOTION SCOUT TIA V5.5 (All versions), SIMOTION SCOUT TIA V5.6 (All versions < V5.6 SP1 HF7), SIMOTION SCOUT TIA V5.7 (All versions < V5.7 SP1 HF1), SIMOTION SCOUT V5.4 (All versions), SIMOTION SCOUT V5.5 (All versions), SIMOTION SCOUT V5.6 (All versions < V5.6 SP1 HF7), SIMOTION SCOUT V5.7 (All versions < V5.7 SP1 HF1), SINAMICS STARTER V5.5 (All versions), SINAMICS STARTER V5.6 (All versions), SINAMICS STARTER V5.7 (All versions < V5.7 HF2). The affected application contains a XML External Entity Injection (XXE) vulnerability while parsing specially crafted XML files. This could allow an attacker to read arbitrary files in the system.
CVE-2011-20001 1 Siemens 3 Simatic, Simatic S7-1200, Simatic S7-1200 Cpu 2026-04-15 7.5 High
A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.3), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.3). The web server interface of affected devices improperly processes incoming malformed HTTP traffic at high rate. This could allow an unauthenticated remote attacker to force the device entering the stop/defect state, thus creating a denial of service condition.
CVE-2024-33497 1 Siemens 1 Simatic Rtls Locating Manager 2026-04-15 6.3 Medium
A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). Affected SIMATIC RTLS Locating Manager Track Viewer Client do not properly protect credentials that are used to authenticate to the server. This could allow an authenticated local attacker to extract the credentials and use them to escalate their access rights from the Manager to the Systemadministrator role.
CVE-2024-33495 1 Siemens 1 Simatic Rtls Locating Manager 2026-04-15 6.5 Medium
A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). The affected application does not properly limit the size of specific logs. This could allow an unauthenticated remote attacker to exhaust system resources by creating a great number of log entries which could potentially lead to a denial of service condition. A successful exploitation requires the attacker to have access to specific SIMATIC RTLS Locating Manager Clients in the deployment.
CVE-2025-40771 1 Siemens 6 Simatic Cp 1542sp-1, Simatic Cp 1542sp-1 Irc, Simatic Cp 1543sp-1 and 3 more 2026-04-15 9.8 Critical
A vulnerability has been identified in SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.4.24), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.4.24), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.4.24). Affected devices do not properly authenticate configuration connections. This could allow an unauthenticated remote attacker to access the configuration data.
CVE-2024-33496 1 Siemens 1 Simatic Rtls Locating Manager 2026-04-15 6.3 Medium
A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). Affected SIMATIC RTLS Locating Manager Report Clients do not properly protect credentials that are used to authenticate to the server. This could allow an authenticated local attacker to extract the credentials and use them to escalate their access rights from the Manager to the Systemadministrator role.